Pump Head Calculation: TDH Formula, Friction Loss & Worked Example

A total dynamic head calculation determines the head a pump must add to move liquid between defined system boundaries at a specified flow. Add the elevation difference, pressure-head difference, velocity-head difference, and hydraulic losses. Calculate friction at the required flow rather than treating TDH as one fixed property of the piping.

This guide works through a water-transfer system delivering 50 m³/h between two open tanks. The elevation difference is 18 m. Suction losses, discharge losses, and a specified equipment pressure drop bring the required pump head to 37.85 m. The example also shows how to build a system curve and reproduce the calculations in Excel.

The total dynamic head formula

For steady incompressible flow between system boundaries 1 and 2, with one pump and no turbine:

Hpump = (z₂ − z₁) + (p₂ − p₁)/(ρg) + (v₂² − v₁²)/(2g) + ΣhL

TermMeaningUnit
z₂ − z₁Destination minus source elevationm
(p₂ − p₁)/(ρg)Boundary pressure difference expressed as liquid headm
(v₂² − v₁²)/(2g)Boundary velocity-head changem
ΣhLPipe, fitting, valve, and equipment lossesm
ρ and gLiquid density and gravitational accelerationkg/m³ and m/s²

The velocity term shown uses the usual turbulent-flow kinetic-energy approximation. Other profiles may need correction factors. For two large tanks, surface velocities are normally negligible. If both gas spaces are at the same atmospheric pressure, their pressure terms cancel.

The Hydraulic Institute system-curve resource explains how required system head changes with flow and operating conditions. “Total head” is the preferred terminology in that resource; TDH is a widely used engineering label.

Choose boundaries before adding losses

Draw the source, pump, piping, equipment, and destination. Mark the points where pressure, elevation, and velocity are defined. For tank-to-tank duty, use the liquid surfaces and include all losses along the connecting flow path.

The pump’s elevation does not create an extra net static-head term between fixed source and destination liquid surfaces. It affects suction conditions and NPSH, but the overall elevation difference is still destination surface minus source surface.

If the destination is a pipe outlet or nozzle, its velocity may be nonzero. If liquid discharges into a large tank, use a consistent exit-loss treatment and negligible tank-surface velocity. Do not count the same dissipation as both an exit loss and an extra retained velocity term.

A closed recirculating loop requires a different boundary interpretation: net elevation around the complete loop cancels, although local pressures and component losses remain important. Building height alone is not the pump head for a fully filled closed loop.

Calculate suction and discharge friction separately

For each uniform pipe section:

v = 4Q/(πD²)

Re = ρvD/μ

hL = (fDL/D + ΣK)v²/(2g)

Q is volumetric flow in m³/s; D is actual internal diameter in metres; μ is dynamic viscosity in Pa·s; fD is the Darcy friction factor. Each section uses its own velocity. A smaller discharge bore can generate much greater loss than a larger suction line.

For this turbulent-flow example, the Swamee–Jain approximation is:

fD = 0.25/{log10[ε/(3.7D) + 5.74/Re0.9]}²

Use ε and D in the same units. Do not substitute a Fanning factor without conversion. The EPA EPANET documentation describes Darcy–Weisbach friction-factor treatment. For laminar flow, the relevant fully developed circular-pipe relation is 64/Re; transitional conditions need appropriate review.

For a component with supplied differential pressure, convert it to head using h = Δp/(ρg). Obtain the pressure drop at the applicable flow, temperature, and clean or fouled condition. For more piping detail, use our pipe pressure-drop calculator.

Worked example: 50 m³/h between open tanks

InputValue
Flow50 m³/h
Density998 kg/m³
Dynamic viscosity0.001 Pa·s
Gravity9.81 m/s²
Destination minus source liquid elevation18 m
Tank pressure difference0 Pa
Suction: length / bore / total K8 m / 0.1023 m / 3
Discharge: length / bore / total K100 m / 0.0779 m / 8
Pipe roughness, both lines0.000045 m
Additional equipment pressure drop at 50 m³/h50,000 Pa

Both tanks are large and open to the same atmospheric pressure. K totals are illustrative aggregates, with relevant entrance and exit effects included once. The equipment pressure drop is additional and is not already represented in K. These values are a worked design basis, not recommended allowances for all systems.

Step 1: Convert flow

Q = 50/3600 = 0.0138889 m³/s

Step 2: Calculate suction loss

For the 0.1023 m bore, velocity is 1.690 m/s, Reynolds number is 172,517, and Darcy friction factor is 0.01889.

hsuction = (0.018886 × 8/0.1023 + 3) × 1.689765²/(2 × 9.81) = 0.652 m

Step 3: Calculate discharge loss

For the 0.0779 m bore, velocity is 2.914 m/s, Reynolds number is 226,553, and Darcy friction factor is 0.01914.

hdischarge = (0.019138 × 100/0.0779 + 8) × 2.914088²/(2 × 9.81) = 14.096 m

Step 4: Convert equipment pressure drop

hequipment = 50000/(998 × 9.81) = 5.107 m

Step 5: Sum required head

TDH = 18 + 0 + 0 + 0.6515 + 14.0959 + 5.1071 = 37.85 m

The three zero-or-nonzero groups correspond to elevation, boundary pressure and velocity, and losses. The required duty point is therefore 50 m³/h at approximately 37.85 m head under these conditions.

If the receiving tank instead needs 150 kPa gauge pressure while the source remains open, add 150000/(998 × 9.81) = 15.32 m. Required head then becomes 53.18 m, with other inputs unchanged.

Check hydraulic power and pump efficiency

Phydraulic = ρgQH = 5.147 kW

If pump efficiency were an illustrative 70% at this duty point:

Pshaft = 5.147/0.70 = 7.35 kW

This is not a final motor rating. Review the selected pump’s absorbed-power curve across its operating range, liquid properties, drive losses, and motor requirements. Do not add pump internal hydraulic loss to the system TDH and then account for it again through pump efficiency.

The existing pump calculations spreadsheet listing describes related head and power calculations. Check its stated scope against your application.

Build a system curve instead of choosing one oversized head

Recalculate at several flows. In this demonstration, the equipment pressure drop is assumed to vary with flow squared around the stated 50 m³/h point. Pipe friction factors are recalculated at every flow.

Flow, m³/hSystem head, m
3025.33
4030.84
5037.85
6046.38

The curve approaches the 18 m boundary head as flow tends toward zero under these assumptions. A centrifugal pump’s operating point is found where its applicable pump curve intersects the system curve. Merely selecting a pump whose maximum head exceeds 37.85 m does not show that it will deliver 50 m³/h.

Check high and low source levels, destination pressure variations, fouled equipment, parallel operation, and control-valve conditions. Do not use a quadratic equipment model where vendor data indicates another relationship.

Excel layout for the TDH calculation

Use B2 = flow in m³/h, B3 = density, B4 = viscosity, B5 = gravity, B6 = elevation difference, B7 = boundary pressure difference in Pa, and B8 = additional equipment pressure drop in Pa. Enter 50, 998, 0.001, 9.81, 18, 0, and 50000 respectively.

Create a pipe table with headings in row 11: A = section, B = length, C = bore, D = roughness, E = K, F = velocity, G = Reynolds number, H = Darcy factor, I = loss head. Use row 12 for suction and row 13 for discharge.

CellFormula
F12=4*($B$2/3600)/(PI()*C12^2)
G12=$B$3*F12*C12/$B$4
H12=IF(G12<2000,64/G12,IF(G12>4000,0.25/(LOG10(D12/(3.7*C12)+5.74/G12^0.9)^2),NA()))
I12=(H12*B12/C12+E12)*F12^2/(2*$B$5)
B16: pipe/fitting loss=SUM(I12:I13)
B17: pressure-boundary head=B7/(B3*B5)
B18: equipment head=B8/(B3*B5)
B19: tank-to-tank TDH=B6+B16+B17+B18
B20: hydraulic power, kW=B3*B5*(B2/3600)*B19/1000

Copy F12:I12 down to row 13. The dollar signs preserve the fluid-property references. B19 assumes negligible endpoint velocities. Add a separate velocity-head term when the selected boundaries require it.

Validate positive flow, density, viscosity, diameter, and gravity; use nonnegative length, roughness, and loss coefficients. Elevation and boundary pressure difference can be negative. The transitional-flow flag is intentional. Zero-flow system-curve endpoints should be handled separately rather than dividing by zero in Reynolds-based formulas.

Checking head from pump suction and discharge gauges

For measured static pressures close to the pump nozzles:

Hmeasured = (pd − ps)/(ρg) + (vd² − vs²)/(2g) + (zd − zs)

Include elevation and velocity differences between measurement sections. If taps are remote, correct for intervening losses. Use consistently referenced pressures and account for sensing-line effects.

Do not add the full external system losses again to measured pump head. The measured pressure rise already reflects the operating duty. Conversely, discharge gauge pressure alone is not pump head: suction pressure may be positive or negative.

NPSH is a separate suction-pressure assessment, not a quantity to add to TDH. Review our suction-line and NPSH guide for that calculation.

Separate process allowances from calculation errors

Allowances should identify a physical reason: an exchanger’s dirty pressure drop, an uncertain pipe route, a known future operating case, or a control-valve pressure requirement. If the equipment input already represents a fouled condition, adding another generic fouling percentage can double-count it. Keep normal and limiting cases in separate columns.

A change in liquid density changes the pressure associated with a given head and affects hydraulic power. A change in viscosity can also change friction and pump performance. It is therefore incomplete to reuse a water calculation for a viscous process liquid by adjusting density alone. Confirm whether the pump manufacturer’s curve needs viscosity correction.

Pipe dimensions deserve particular attention during design revisions. A nominal three-inch line does not uniquely identify internal bore; schedule and lining matter. Valves should reflect the actual flow path and position, not just the count of symbols on a drawing. For branches, use the flow through each branch rather than assigning total plant flow to every pipe.

Finally, keep operational controls in the model. A throttling valve contributes loss that changes with its position. A variable-speed pump changes the pump curve. Neither control method makes the underlying static elevation or process-pressure requirement disappear. Evaluate the intended control range against allowable pump operation, minimum flow, NPSH, and absorbed power.

Frequently asked questions

1. Is TDH just the vertical lift?

No. It also includes pressure requirements, velocity changes, and losses at the specified flow.

2. Should suction friction be included?

Yes, when calculating the complete source-to-destination duty. Use the suction line’s own bore, velocity, and fittings.

3. Can gauge pressure be used?

For a pressure difference, yes, if both values share the same reference. Absolute pressure remains necessary for calculations such as NPSH.

4. Does pump elevation change static system head?

Not between fixed tank surfaces. It changes suction conditions, while the tank-to-tank elevation difference stays the same.

5. Is TDH constant?

No. Losses usually change with flow, and tank levels or vessel pressures can also change.

6. Can I add a large percentage margin?

Use documented allowances tied to actual uncertainties. An arbitrary increase can shift the operating point, raise energy use, and create control problems.

7. Is a workbook attached?

This article provides copyable formulas and a worksheet layout; it does not include a newly generated downloadable Excel file.

Specify flow and head together

The example requires 37.85 m TDH at 50 m³/h. Retain the component breakdown, evaluate the operating envelope, and compare the resulting system curves with vendor pump performance. Explore further engineering resources at GrowMechanical.